INSTALLATION & MAINTENANCE MANUAL PRIMERA® HOT WATER SUPPLY BOILER MODELS: 400B, 540B, 750B, 1000B, 1200B, 1600B & 2000B PRIMERA® WATER HEA
34-50 04/02/2010 10Gas Connection 1. Safe operation of unit requires adequate gas supply with the required static and dynamic (flow) pressures.
34-50 04/02/2010 11WATER CONNECTIONS AND PIPE SIZE Inlet and Outlet Connections The inlet and outlet water connections to the unit are cupronickel
34-50 04/02/2010 12 If the temperature rise is too high, then the water velocity is too low. Check the following: 1. Check for restric
34-50 04/02/2010 13BOILER FLOW RATE REQUIREMENTS BOILER FLOW RATE REQUIREMENTS AND FACTORY SUPPLIED* CIRCULATOR PUMP PERFORMANCE Model Circulator
34-50 04/02/2010 14Important For Hydronic Heating Applications: 1. Design flow rate is the maximum allowable and recommended flow through the he
34-50 04/02/2010 15GENERAL INFORMATION Temperature Setting (For Domestic Hot Water Use) This unit has an adjustable thermostat to control water te
34-50 04/02/2010 16Cathodic Protection In hot water systems utilizing cathodic protection, Hydrogen gas can be produced when the hot water system
34-50 04/02/2010 17REMOTE CONNECTIONS - TERMINAL STRIP A terminal strip for the remote connection is located behind the control panel and is acces
34-50 04/02/2010 18BOILER MANAGEMENT SYSTEM (BMS) CONNECTION Refer to above picture for all applications If BMS is to provide
34-50 04/02/2010 19SEQUENCE OF OPERATION - IGNITION CONTROL 1. POWER-UP Power is applied to the full time 24 volt input. The microprocessor will s
34-50 04/02/2010 2 PRODUCT SAFETY INFORMATION REFRACTORY CERAMIC FIBER PRODUCT WITH CRYSTALLINE SILICA WARNIN
34-50 04/02/2010 20TO TURN OFF GAS TO APPLIANCE 1. Turn off all electric power to the appliance if service is to be performed. 2. Locate manual
34-50 04/02/2010 21PERIODIC MAINTENANCE Listed below are items that must be checked to insure safe reliable operations. Maintenance must be perfor
34-50 04/02/2010 22i. Tag to identify then disconnect wires to the gas valve, blower, pressure switches, etc., as required to remove the blower a
34-50 04/02/2010 23HEATING BOILER SYSTEM PIPING: Primary-Secondary Piping For highest reliability and temperature accuracy, plumb PRIMERA® boilers
34-50 04/02/2010 24
34-50 04/02/2010 25Piping Schematic for Multiple PRIMERA® Boilers - Primary-Secondary Circulator (confirm proper sizing) Full Port Isolation Ball
34-50 04/02/2010 26
34-50 04/02/2010 27
34-50 04/02/2010 28
34-50 04/02/2010 29 Piping Schematic for Two PRIMERA® Water Heaters and Two Storage Tanks Notes: 1. All piping to the storage tanks must be balan
34-50 04/02/2010 3 IMPORTANT SAFETY NOTE It takes only 5 seconds of skin contact with 140°F water to cause a second degree burn! You must pro
34-50 04/02/2010 30
34-50 04/02/2010 31
34-50 04/02/2010 4CODES The equipment shall be installed in accordance with those installation regulations in force in the local area where the in
34-50 04/02/2010 5CLEARANCES TO COMBUSTIBLE SURFACES The appliance must not be installed on a combustible floor, on carpet, on other combustible f
34-50 04/02/2010 6NOTE: This unit may be installed with an optional remote air intake system which uses a make-up air duct to draw combustion
34-50 04/02/2010 7Through-the Wall Vent Termination (Category III) The product uses the positive pressure generated by the burner system blower to
34-50 04/02/2010 8Combustion air supplied from outdoors must be free of contaminants (See Combustion and Ventilation Air). Remote Combustion Air
34-50 04/02/2010 9The combustion products outlet must be located at least 4 feet (1.22 m) below, 4 feet (1.22 m) horizontally from or 1 foot (0.3